Technical data
Conductor resistance
max 57,1 Ohm/km at 20°
Operating temperature
Fixed installation -30 C°/+70 C°
Voltage test
3,6 kV
Impedance
150 Ohm +/- 10%
Radius of curvature
mobile installation 15 times the external diameter
Cable structure
Conductors
in red copper insulated in PE
Color
red – green
External sheath
· Violet PVC (internal)
· Black PE (external)
· Purple polyurethane (mobile installation)
Shielding
aluminum sheet plus tinned copper stocking cover-up 100%
Utilization
Cable suitable for the connection of L2-Bus system components according to Profibus standards according to DIN 19245-T3 and EN 50170. Used to exchange information between different automation systems and to connect decentralized serial units.
Date of update 20/07/2017
| code | cable formation | color | external diameter |
|---|---|---|---|
| EQBL | 1x2x0,64 | violet | 8 |
We design and manufacture electrical cables for automation to customer specifications